# CANEO series5x + Beckhoff EL6224 — IO-Link Integration Guide

This guide walks through integrating a **CANEO series5x Duo-Touch Display** with a **Beckhoff EL6224** IO-Link terminal in TwinCAT 3. By the end you'll be reading touch inputs from the button and writing text, numbers, text color, and LED scenes to it from your PLC program — all through a single reusable function block (FB) that hides the byte-level plumbing.

The tricky part of an IO-Link integration on the EL6224 is that the terminal exposes process data as a flat array of individual bytes, while several of the CANEO series5x parameters (the active scene, the displayed number, and the text string) are **larger than one byte**. This guide shows how to stitch those multi-byte fields back together using TwinCAT DUTs and unions, so you can write to one clean variable instead of juggling raw bytes.

## Prerequisites

Before starting, make sure:

- An **EL6224** IO-Link terminal is installed in your EtherCAT node (e.g., behind an EK1200 coupler) and appears under **I/O → Devices** in TwinCAT.
- **TwinCAT 3** is installed and can go online with the controller.
- The **CANEO series5x Duo-Touch Display** is wired to an IO-Link port on the EL6224 (this example uses **port 1**).
- You have the **IODD** file for your CANEO series5x variant (download it from CAPTRON).
- You have the CANEO series5x **IO-Link process data layout** handy — you'll reference it when mapping bytes: [series5x IO-Link Process Data](https://docs.captron.com/trms/series5x/io-link-process-data).

---

## 1. Wire the CANEO series5x into the EL6224

Wire the device leads into the EL6224 following the terminal's connection diagram. This example uses **port 1**.

For pinout, power-contact routing, and status-LED meanings, always refer to the official Beckhoff documentation: [EL6224 manual (PDF)](https://download.beckhoff.com/download/Document/io/ethercat-terminals/el6224_en.pdf).

![EL6224 IO-Link terminal wiring and connection diagram](./images/caneo50-el6224-image1.png)

---

## 2. Import the IODD and scan for the device

Open TwinCAT and **go online** with the controller.

1. In the **Solution Explorer**, navigate to the **EL6224** under **I/O → Devices**.
2. Open the **IO-Link** tab.
3. Click **Import Devicedescription** and select the IODD for your device. This example uses the **CANEO series52 Duo-Touch Display**.
4. Click **Scan devices**. The CANEO series5x should appear on the port it's wired to (port 1 here).

![TwinCAT IO-Link tab with the device catalog and Scan devices button](./images/caneo50-el6224-image2.png)

> **Why import the IODD first?** The IODD tells TwinCAT the device's identity, parameters, and process-data structure. Without it, a scan will still detect *something* on the port, but you won't get the named parameters or the correct process-data layout.

---

## 3. Read the device parameters

Double-click the **port 1** device to open its parameter view, then **read the IODD file** so TwinCAT pulls the current parameter set from the device.

Under the **Parameter** tree you'll see the CANEO series5x configurable items — **Service Functions**, **Touch Input 1 / 2**, **Control Inputs**, **Output**, **Display**, **Scene 1…n**, and so on.

![Port 1 parameter view showing the CANEO series5x IODD parameters](./images/caneo50-el6224-image3.png)

---

## 4. Enable the process data

Once the device is identified, switch back to **General**, then right-click and open **Process Data**.

On the **Process Data** page, tick **Write to System Manager** and **Activate**. You'll see the input and output process data laid out with their bit lengths and offsets.

![Process Data page with Write to System Manager enabled](./images/caneo50-el6224-image4.png)

After activating, the input and output process data populate in the tag columns.

![Online tag columns showing the populated process data](./images/caneo50-el6224-image5.png)

Expand the **iolink card** in the Solution Explorer and you'll see the raw process data broken out byte by byte — **IO-Link Port1_in** as `Port1: process data[0…7]` and **IO-Link Port1_out** as `Port1: process data[0…15]`.

![Solution Explorer tree showing Port1 process data in (0-7) and out (0-15)](./images/caneo50-el6224-image6.png)

> Now we need to link tags to the bytes that correspond to each parameter. Use the [series5x IO-Link process data layout](https://docs.captron.com/trms/series5x/io-link-process-data) as your reference for which byte is which.

---

## 5. The multi-byte problem

The EL6224 exposes process data as individual bytes, but several CANEO series5x fields **span more than one byte**:

- **Active Scenes** — 2 bytes (`INT`)
- **Number to Display** — 4 bytes (`UDINT`)
- **Text to Display** — up to 6 bytes (a string)

You can't cleanly write a two- or four-byte value into single-byte process-data tags one at a time. To get around this, we combine the bytes into one variable using a **DUT** (Data Unit Type) built as a **union**.

A union overlays two views of the same memory: a friendly typed field (like an `INT` or a `STRING`) and a raw `ARRAY … OF BYTE` occupying the exact same bytes. Write the typed field, and TwinCAT automatically fills the byte array for you — no manual bit-shifting.

Create three DUTs.

### `ActiveScenes_Struct`

A 2-byte value (`INT`) overlaid with a 2-byte array.

```
TYPE ActiveScenes_Struct :
UNION
    num   : INT;
    bytes : ARRAY[0..1] OF USINT;
END_UNION
END_TYPE
```

![ActiveScenes_Struct DUT defined as a union](./images/caneo50-el6224-image7.png)

### `DisplayedNumber_Struct`

A 4-byte value (`UDINT`) overlaid with a 4-byte array.

```
TYPE DisplayedNumber_Struct :
UNION
    num   : UDINT;
    bytes : ARRAY[0..3] OF USINT;
END_UNION
END_TYPE
```

![DisplayedNumber_Struct DUT defined as a union](./images/caneo50-el6224-image8.png)

### `StringToBytes`

A 5-character string overlaid with a 6-byte array.

```
TYPE StringToBytes :
UNION
    str   : STRING(5);
    bytes : ARRAY[0..5] OF BYTE;
END_UNION
END_TYPE
```

![StringToBytes DUT defined as a union](./images/caneo50-el6224-image9.png)

### Bundling it all: `series5x_PDout` and `series5x_PDin`

The three unions above solve the multi-byte problem, but on their own they leave you with a long, flat list of loose variables in the GVL — and that list repeats for every device you add. A second, cleaner step is to wrap one device's entire process-data image into two **structs**: one for everything you send *to* the display, one for everything you read *from* it.

These are ordinary `STRUCT` DUTs (not unions). They don't change how the data is packed — they just group it.

#### `series5x_PDout` — everything you write to the device

```
TYPE series5x_PDout :
STRUCT
    TextToDisplay : STRING(5);                          //value you write to
    stringToBytes : StringToBytes;                      //link raw data
    DisplayedNumber : UDINT;                            //value you write to
    displayedNumberStuct : DisplayedNumber_Struct;      //link raw data
    TextColor AT %Q* : USINT;
    TextSelect AT %Q*: USINT;
    ActiveScenes : INT;                                 // value you write to
    activeScenesSctruct : ActiveScenes_Struct;          //link raw data
    Mode AT %Q*: USINT;
END_STRUCT
END_TYPE
```

![The series5x_PDout struct with clean values paired with their raw-data unions](./images/caneo50-el6224-image16.png)

Read the member list as **pairs**. Each multi-byte field appears twice, and the two halves do different jobs:

<table>
  <thead>
    <tr>
      <th>Member</th>
      <th>Type</th>
      <th>Role</th>
    </tr>
  </thead>
  <tbody>
    <tr><td><code>TextToDisplay</code></td><td><code>STRING(5)</code></td><td>The value <b>you write</b> in your program</td></tr>
    <tr><td><code>stringToBytes</code></td><td><code>StringToBytes</code></td><td>The union <b>you link</b> to raw process data</td></tr>
    <tr><td><code>DisplayedNumber</code></td><td><code>UDINT</code></td><td>The value <b>you write</b></td></tr>
    <tr><td><code>displayedNumberStuct</code></td><td><code>DisplayedNumber_Struct</code></td><td>The union <b>you link</b></td></tr>
    <tr><td><code>ActiveScenes</code></td><td><code>INT</code></td><td>The value <b>you write</b></td></tr>
    <tr><td><code>activeScenesSctruct</code></td><td><code>ActiveScenes_Struct</code></td><td>The union <b>you link</b></td></tr>
    <tr><td><code>TextColor</code></td><td><code>USINT AT %Q*</code></td><td>Single byte — write and link are the same variable</td></tr>
    <tr><td><code>TextSelect</code></td><td><code>USINT AT %Q*</code></td><td>Single byte — write and link are the same variable</td></tr>
    <tr><td><code>Mode</code></td><td><code>USINT AT %Q*</code></td><td>Single byte — write and link are the same variable</td></tr>
  </tbody>
</table>

The three single-byte members (`TextColor`, `TextSelect`, `Mode`) carry an `AT %Q*` address and need no partner, because a one-byte value maps straight onto one process-data byte. The three multi-byte fields can't do that, so each one keeps its plain typed member for you to write to and its union member for the mapping to attach to. The function block is what copies between the two halves of each pair.

#### `series5x_PDin` — everything you read from the device

```
TYPE series5x_PDin :
STRUCT
    Caneoseries5x_TouchZone1 AT %I* : USINT;
    Caneoseries5x_TouchZone2 AT %I* : USINT;
    Caneoseries5x_TouchZone3 AT %I* : USINT;
    Caneoseies5x_TouchZone4 AT %I* : USINT;
END_STRUCT
END_TYPE
```

![The series5x_PDin struct with four touch zones each mapped to an input byte](./images/caneo50-el6224-image17.png)

The input side is simpler. Every touch zone is a single byte, so there are no unions here at all — just four `USINT` members with `AT %I*` addresses, one per touch zone. This version covers four zones; trim or extend the list to match the number of zones your button actually has.

> **Why bundle at all?** With these two DUTs you declare **one instance of each per device** instead of twenty-odd loose globals — for example `caneoSeries52_PDout_port1 : series5x_PDout;` and `caneoSeries52_PDin_port1 : series5x_PDin;`. Adding a second display becomes two more declarations rather than another twenty renamed variables, the mapping tree in TwinCAT groups every byte under its port's instance name, and you can pass a whole device's process data into a function block as a single argument.

---

## 6. Declare the GVL variables

**Activate the configuration**, then open the **GVL** (Global Variable List).

First declare the raw bytes for the three multi-byte fields. These are the variables the output process data links to, and they're called *bytes* because they hold raw data that the function block assembles from the unions. Give each one an `AT %Q*` address so it maps to output process data.

```
ActiveScenes_byte0_port1 AT %Q* : USINT;
ActiveScenes_byte1_port1 AT %Q* : USINT;

Number_byte0_port1 AT %Q* : USINT;
Number_byte1_port1 AT %Q* : USINT;
Number_byte2_port1 AT %Q* : USINT;
Number_byte3_port1 AT %Q* : USINT;

String_byte0_port1 AT %Q* : USINT;
String_byte1_port1 AT %Q* : USINT;
String_byte2_port1 AT %Q* : USINT;
String_byte3_port1 AT %Q* : USINT;
String_byte4_port1 AT %Q* : USINT;
String_byte5_port1 AT %Q* : USINT;
```

![GVL declarations for the ActiveScenes, Number, and String bytes](./images/caneo50-el6224-image18.png)

Only the three multi-byte fields need bytes like this. `Mode`, `TextSelect`, and `TextColor` are absent because a one-byte value maps straight onto one process-data byte and needs no union — they're handled in step 8. It's worth pasting the byte-to-process-data mapping from the next step into the GVL as a comment block while you're here; it's the one place that records which byte goes where.

---

## 7. Link the process data bytes

Go back to the **IO-Link Port1_out** process data in the Solution Explorer and link each GVL byte to the correct process-data byte position.

Open a byte's link dialog and pick the matching `Port1 process data[n]`.

![Linking a GVL byte to a Port1 output process data byte](./images/caneo50-el6224-image11.png)

> **If the variables don't show up** in the link dialog, make sure you activated the configuration after adding them to the GVL.

Use this mapping for the **output** process data:

<table>
  <thead>
    <tr>
      <th>GVL variable</th>
      <th>Output process data byte</th>
    </tr>
  </thead>
  <tbody>
    <tr><td><code>ActiveScenes_byte1_port1</code></td><td><code>processdata[13]</code></td></tr>
    <tr><td><code>ActiveScenes_byte0_port1</code></td><td><code>processdata[12]</code></td></tr>
    <tr><td><code>Number_byte3_port1</code></td><td><code>processdata[11]</code></td></tr>
    <tr><td><code>Number_byte2_port1</code></td><td><code>processdata[10]</code></td></tr>
    <tr><td><code>Number_byte1_port1</code></td><td><code>processdata[9]</code></td></tr>
    <tr><td><code>Number_byte0_port1</code></td><td><code>processdata[8]</code></td></tr>
    <tr><td><code>String_byte5_port1</code></td><td><code>processdata[5]</code></td></tr>
    <tr><td><code>String_byte4_port1</code></td><td><code>processdata[4]</code></td></tr>
    <tr><td><code>String_byte3_port1</code></td><td><code>processdata[3]</code></td></tr>
    <tr><td><code>String_byte2_port1</code></td><td><code>processdata[2]</code></td></tr>
    <tr><td><code>String_byte1_port1</code></td><td><code>processdata[1]</code></td></tr>
    <tr><td><code>String_byte0_port1</code></td><td><code>processdata[0]</code></td></tr>
  </tbody>
</table>

---

## 8. Declare the PDin and PDout objects

Back in the **GVL**, below the bytes, add the only other thing this device needs — **one object of each DUT**, named after the port they serve.

```
caneoSeries52_PDin_port1 : series5x_PDin;
caneoSeries52_PDout_port1: series5x_PDout;
```

![GVL with the PDin and PDout objects declared below the byte variables](./images/caneo50-el6224-image12.png)

Everything else comes with them: the clean values you write, the unions the function block packs them through, the single-byte outputs, and the touch-zone inputs are all members of these two objects.

---

## 9. Build the `Caneoseries5x_AOI` function block

Now we pack the clean values into the raw output bytes. Create a **Function Block** called **`Caneoseries5x_AOI`**.

It needs no local variables — the unions already live inside `caneoSeries52_PDout_port1`, so leave the declaration part as TwinCAT creates it and write everything in the body.

The body does the same job in two moves per field: copy the clean value into the union's typed member, then copy the union's raw bytes out to the linked byte variables. TwinCAT fills the byte view for you — so writing one value (e.g. `gvl.caneoSeries52_PDout_port1.ActiveScenes`) ends up addressing multiple process-data bytes.

```
gvl.caneoSeries52_PDout_port1.activeScenesSctruct.num := gvl.caneoSeries52_PDout_port1.ActiveScenes;

gvl.ActiveScenes_byte0_port1 := gvl.caneoSeries52_PDout_port1.activeScenesSctruct.bytes[1];
gvl.ActiveScenes_byte1_port1 := gvl.caneoSeries52_PDout_port1.activeScenesSctruct.bytes[0];

//displayed number
gvl.caneoSeries52_PDout_port1.displayedNumberStuct.num := gvl.caneoSeries52_PDout_port1.DisplayedNumber;

gvl.Number_byte0_port1 := gvl.caneoSeries52_PDout_port1.displayedNumberStuct.bytes[3];
gvl.Number_byte1_port1 := gvl.caneoSeries52_PDout_port1.displayedNumberStuct.bytes[2];
gvl.Number_byte2_port1 := gvl.caneoSeries52_PDout_port1.displayedNumberStuct.bytes[1];
gvl.Number_byte3_port1 := gvl.caneoSeries52_PDout_port1.displayedNumberStuct.bytes[0];

gvl.caneoSeries52_PDout_port1.stringToBytes.str := gvl.caneoSeries52_PDout_port1.TextToDisplay;

gvl.String_byte0_port1 := gvl.caneoSeries52_PDout_port1.stringToBytes.bytes[0];
gvl.String_byte1_port1 := gvl.caneoSeries52_PDout_port1.stringToBytes.bytes[1];
gvl.String_byte2_port1 := gvl.caneoSeries52_PDout_port1.stringToBytes.bytes[2];
gvl.String_byte3_port1 := gvl.caneoSeries52_PDout_port1.stringToBytes.bytes[3];
gvl.String_byte4_port1 := gvl.caneoSeries52_PDout_port1.stringToBytes.bytes[4];
gvl.String_byte5_port1 := gvl.caneoSeries52_PDout_port1.stringToBytes.bytes[5];
```

![Caneoseries5x_AOI function block declaration and mapping body](./images/caneo50-el6224-image13.png)

> **Watch the byte order — it differs per field, and all three cases matter.**<br/>
> **ActiveScenes** is byte-swapped: `byte0` takes `bytes[1]`, `byte1` takes `bytes[0]`.<br/>
> **Number** is fully reversed: `byte0` takes `bytes[3]`, down to `byte3` taking `bytes[0]`.<br/>
> **String** is straight through: `byte0` takes `bytes[0]`.<br/>
> These orderings are what the CANEO series5x expects. Copy them exactly.

---

## 10. Call the function block from your program

In your main program, declare a local instance of the function block:

```
VAR
    caneoseries5x : Caneoseries5x_AOI;
END_VAR
```

![Main program local variable declaring a Caneoseries5x_AOI instance](./images/caneo50-el6224-image14.png)

---

## 11. Write to the display

Call the function block, then write to the members of `caneoSeries52_PDout_port1`. The function block packs them into the process data on the next scan.

```
caneoseries5x();

gvl.caneoSeries52_PDout_port1.Mode := 1;
gvl.caneoSeries52_PDout_port1.TextColor := 1;
gvl.caneoSeries52_PDout_port1.DisplayedNumber := 12345;
gvl.caneoSeries52_PDout_port1.TextSelect := 1;
gvl.caneoSeries52_PDout_port1.ActiveScenes := 1;
```

![EXECUTE rung calling the function block and writing values to the process data](./images/caneo50-el6224-image15.png)

Notice that every write goes through the one instance — there are no per-field global names to remember, and pointing this block at a second display means changing the instance name and nothing else.

In this example we switched **Mode** to accept process data (`Mode := 1`), set a **Text Select** code, a **Text Color**, a **Displayed Number** of `12345`, and an **Active Scenes** value. To display your own text instead of a built-in string, write to `TextToDisplay` as well — the function block copies it through `stringToBytes` for you:

```
gvl.caneoSeries52_PDout_port1.TextToDisplay := 'hello';
```

For the meaning of each value — the mode options, text-select codes, color codes, and the scene bitmask — reference the [series5x IO-Link process data layout](https://docs.captron.com/trms/series5x/io-link-process-data).

---

## Reference

- **CANEO series5x IO-Link process data:** [https://docs.captron.com/trms/series5x/io-link-process-data](https://docs.captron.com/trms/series5x/io-link-process-data)
- **Beckhoff EL6224 manual (PDF):** [https://download.beckhoff.com/download/Document/io/ethercat-terminals/el6224_en.pdf](https://download.beckhoff.com/download/Document/io/ethercat-terminals/el6224_en.pdf)

---

## Download: example project

Download the ready-made TwinCAT objects used in this guide — the DUTs, the GVL, and the `Caneoseries5x_AOI` function block. Unzip it and add the objects to your TwinCAT project.

<a href="/downloads/BeckhoffCaneoSeries5xFB.zip" target="_blank">BeckhoffCaneoSeries5xFB.zip</a>