Events & Commands
Events
| Event Code | Type | Definition and recommended maintenance action |
|---|---|---|
| 6144 | Error | Output Overload – Output current too high – max. 200 mA |
| 6145 | Error | Voltage Output Overload – Current on analog voltage output too high |
| 6146 | Warning | Current Output Overload – Resistance on current output too high |
| 16912 | Warning | Device temperature over-run (above 90°C) – Clear source of heat |
| 16928 | Warning | Device temperature under-run (below -20°C) – Insulate device |
| 20496 | Error | Component malfunction – Repair or exchange |
| 20752 | Warning | Primary supply voltage over-run (above 30V) – Check tolerance |
| 20753 | Warning | Primary supply voltage under-run (below 16.8V) – Check tolerance |
| 25376 | Error | Parameter error – Check data sheet and values |
Commands
ISDU Index 2 – System Command
General Commands
| Value | Name | Description |
|---|---|---|
| 128 | Device Reset | Restart the device |
| 130 | Restore Factory Settings | Restore Factory Settings |
Calibration Commands
| Value | Name | Description |
|---|---|---|
| 164 | Container Teach In 'Low' | Stores the current sensor value as Low Level reference point |
| 165 | Container Teach In 'High' | Stores the current sensor value as High Level reference point |
| 166 | Calculate Dielectric Constant | Calculate Medium Dielectric Constant from Capacitance of High and Low Level Reference points |
| 167 | Set Additional Reference 1 | Stores the current sensor value as additional reference point 1 |
| 168 | Set Additional Reference 2 | Stores the current sensor value as additional reference point 2 |
| 169 | Set Additional Reference 3 | Stores the current sensor value as additional reference point 3 |
| 170 | Set Additional Reference 4 | Stores the current sensor value as additional reference point 4 |
| 171 | Perform One-Click Teach-In | Note: will change Low and High reference points |
| 172 | Adjust to changed medium | Note: will change High reference point |