Skip to main content

Self-Diagnosis and Error Codes

The SENSORswitch includes the following diagnosis features:

  • Self-Test: When triggered by the respective IO-Link System Command:
    • The capacitive measurement circuit is stimulated, producing an "actuation" for 200 ms
    • The RGB LED is checked electrically
  • Monitoring of Supply Voltage and MCU Temperature
  • Output Overload Detection

Detected errors are indicated via IO-Link Events and/or in the Error Code IO-Link Parameter, as well as by blinking patterns of the LED.

Error Codes

Blink CodeIO-Link Error CodeDescription
10x0001Internal error
50x0010Test of capacitive sensor failed
80x0080Memory error
120x0800LED error
130x1000Overload error on digital output

Revision History

Rev. A – 2021-07-09

  • Initial release with HTML documents for each CANEO series4x variant

Rev. B – 2022-06-23

  • Unified document for all CANEO series4x variants

Rev. C – 2023-08-07

  • Added introduction, section Self-Diagnosis and Error Codes, and legal and trademark notice
  • Added explanation for IO-Link Process Data bit indexing and length of ISDUs
  • Document layout changed to A4 format

Rev. D – 2024-05-02

  • More clear explanation of selection of LED Control Mode / IO-Link Process Data output
  • Marked "o" as a Displayable Character
  • Correct assignment of Device IDs to variants

Rev. E – 2024-10-11

  • Added illustration of LED indexing
  • Added illustration of each Process Data structure